After winter, what maintenance should be done for the fruit chiller?

After winter, what maintenance should be done for the fruit chiller?


1. When the fruit preservation cabinet needs to be opened again after a long time stop, you should wait at least 3 hours before operating the fruit preservation cabinet for temperature control.


Principle: As the compressor lubricant needs to be heated before the unit can be properly lubricated, so only the electric oil heater on the main gate can be started, and the heater will be automatically cut off after the unit is normally started. Remember, this is very important, otherwise the good quality compressor will be damaged by lack of oil.


2. winter is coming, if the fruit preservation cabinet off not to use, we should drain the water in the cooling tower, to prevent the winter fruit preservation cabinet stopped after the cooling tower water icing damage to the condenser.